LIGHT OIL BURNERS TWO STAGES FBR Surabaya

FGP 50/2 EVO
Burners for light-oil two stages.
They are composed by: fan at high pressurisation and reversed blades, combustion head with adjustment at high efficiency and high flame stability and hydraulic system of regulation combustive air on the two stages of flame.

Compact overall dimensions and disposition rationalized of the components with accessibility facilitated for the operations of setting and maintenance.
Complete of nozzle, flexible pipes and line filter.
Complete of flange and gasket for installation on generator.
Fig. 1 FGP 50/2 EVO
SK070002_A_en
LIGHT-OIL BURNERS TWO STAGES
FGP 50/2 EVO
TECHNICAL DATA FGP 50/2 EVO
* Reference conditions: Environment temperature 20°C – Barometric pressure 1013 mbars – Altitude 0 metre (sea level).
** Measured sonourous pressure in the combustion lab, with funcional burner on beta boiler in a distance of 1 m (UNI EN ISO 3746).
*** For burner FGP 50/2 with long head add 1 kg to the weight.
OPERATING RANGE DIAGRAM FGP 50/2 EVO
MODEL FGP 50/2 EVO
Flow min. 1°st. / min. 2°st. – max. 2°st. * [kg/h] 9.9/20-53.1
Thermal power min. 1°st. / min. 2°st. –
max. 2°st. *
[Mcal/h] 100.1/204-541.8
Thermal power min. 1°st. / min. 2°st. –
max. 2°st. *
[kW] 117.4/237-630
Fuel: LIGHT-OIL 1.5°E at 20°C = 6.2 cSt = 35 sec Redwood N°1
Intermitted working operation (min. 1 stop every 24 hours) two stages
Environmental conditions operation / storage: -15…+40°C / -20…+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Nominal electric power [kW] 1.1
Fan motor [kW] 0.74
Nominal motor current absorption [A] 1.8
Nominal auxiliary absorption [A] 0.3
Power supply: 3~400V, 1N~230V – 50Hz
Electric protection degree: IP 40
Burner weight *** [kg] 31
Fig. 2 X = Thermal power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the boiler.
For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-compliance,
contact the manufacturer.

 

FLAME TUBE LENGTH
Flame tube length must be selected based on the specifications supplied by boiler manufacturer and, in any case, it
must be greater than the thickness of the boiler door included its insulation.
In case of boilers with flame inversion or front flue combustion chambers, it is necessary to insulate the area between
the flame tube and front door with refractory material. This protection material must not impede flame tube extraction.
** For different flame lengths, please contact our Technical-Sales Department.